mbusd

0

Описание

Open-source Modbus TCP to Modbus RTU (RS-232/485) gateway.

Языки

  • C83,1%
  • Python9%
  • CMake5,7%
  • Shell2%
  • Dockerfile0,2%
README.md

About mbusd

mbusd

mbusd is open-source Modbus TCP to Modbus RTU (RS-232/485) gateway. It presents a network of RTU slaves as single TCP slave.

That is a TCP-Slave (or server) which acts as a RTU-master to get data from Modbus RTU-slave devices.

Features:

  • Small footprint - suitable to run on embedded devices and SBCs like Raspberry Pi
  • Multi-master - multiple TCP masters can access slave devices in RTU network using same gateway
  • Robustness - can retry requests with mismatched response CRC
  • Flexible RTU modes - speed/parity/stop-bits/timeouts can be configured for RTU network
  • Support for both of automatic and manual (using RTS bit) direction control types for RS-485 transceivers

Supported function codes:

  • 01: Read coil status
  • 02: Read input status
  • 03: Read holding registers
  • 04: Read input registers
  • 05: Force single coil
  • 06: Preset single register
  • 07: Read exception status
  • 15: Force multiple coils
  • 16: Preset multiple registers

Please note all other function codes (including vendor-specific extensions) are supported on a "best-effort" basis and most likely will fail.

Installation instructions:

$ git clone https://github.com/3cky/mbusd.git mbusd.git $ cd mbusd.git $ mkdir -p build && cd build $ cmake -DCMAKE_INSTALL_PREFIX=/usr .. $ make $ sudo make install

Compile time options can be altered in many ways, e.g. by using the following tools in the

build
dir:

  • ccmake - usually in the package cmake-curses-gui
  • cmake-gui - usually in the package cmake-qt-gui

Usage:

mbusd [-h] [-d] [-L logfile] [-v level] [-c cfgfile] [-p device] [-s speed] [-m mode] [-S] [-t] [-r] [-y sysfsfile] [-Y sysfsfile] [-A address] [-P port] [-C maxconn] [-N retries] [-R pause] [-W wait] [-T timeout] [-b] -h Usage help. -d Instruct mbusd not to fork itself (non-daemonize). -L logfile Specifies log file name ('-' for logging to STDOUT only, relative path or bare filename will be stored at /var/log, default is /var/log/mbusd.log). -v level Specifies log verbosity level (0 for errors only, 1 for warnings and 2 for informational messages also). If mbusd was compiled in debug mode, valid log levels are up to 9, where log levels above 2 adds logging of information about additional internal events. -c cfgfile Read configuration from cfgfile. -p device Specifies serial port device name. -s speed Specifies serial port speed. -m mode Specifies serial port mode (like 8N1). -S Enable RS-485 support for given serial port device (Linux only) -t Enable RTS RS-485 data direction control using RTS, active transmit. -r Enable RTS RS-485 data direction control using RTS, active receive. -y sysfsfile Enable RS-485 direction data direction control by writing '1' to sysfs file for transmitter enable and '0' to file for transmitter disable. -Y sysfsfile Enable RS-485 direction data direction control by writing '0' to sysfs file for transmitter enable and '1' to file for transmitter disable. -A address Specifies TCP server address to bind (default is 0.0.0.0). -P port Specifies TCP server port number (default is 502). -C maxconn Specifies maximum number of simultaneous TCP connections (default is 32). -N retries Specifies maximum number of request retries (0 disables retries, default is 3). -R pause Specifies pause between requests in milliseconds (default is 100ms). -W wait Specifies response wait time in milliseconds (default is 500ms). -T timeout Specifies connection timeout value in seconds (0 disables timeout, default is 60). -b Instructs mbusd to reply on a broadcast.

Please note running mbusd on default Modbus TCP port (502) requires root privileges!

Configuration file:

mbusd can read the configuration from a file specified by

-c
command line flag. Please see example configuration file for complete list of available configuration options.

systemd:

mbusd has systemd support. The build system detects whether the system has systemd after which

sudo make install
installs the
mbusd@.service
file on systems with systemd active.

The mbusd service can be started via:

# systemctl start mbusd@<serial port>.service

where

<serial port>
is escaped serial port device short name (like
ttyUSB0
for
/dev/ttyUSB0
device name or
serial-rs485
for
/dev/serial/rs485
device name).

mbusd started by systemd will read its configuration from file named

/etc/mbusd/mbusd-<serial port>.conf
. This way it's possible to run multiple mbusd instances with different configurations.

To see the mbusd service status:

# systemctl status mbusd@<serial port>.service

To monitor the mbusd service:

# journalctl -u mbusd@<serial port>.service -f -n 10

To start the mbusd service on system boot:

# systemctl enable mbusd@<serial port>.service

Please check systemd documentation for other usefull systemd commands.

Docker:

mbusd can be launched in Docker container with the following command:

where

/path/to/mbusd.conf
is the path to mbusd config file in the local filesystem.

Contributing:

Reporting bugs

Please file issue with attached debug log in verbose (

-v9
) mode, i.e.:

# mbusd -L/tmp/mbusd.log -p /dev/ttyUSB0 -s 9600 -P 502 -d -v9

Unless you were prompted so or there is another pertinent reason (e.g. GitHub fails to accept the bug report), please do not send bug reports via personal email.

Workflow for code contributions

  1. Fork it and clone forked repository
  2. Create your feature branch (
    git checkout -b my-new-feature
    )
  3. Make your changes
  4. Commit your changes (
    git commit -am 'Add some feature'
    )
  5. Push to the branch (
    git push origin my-new-feature
    )
  6. Create new Pull Request

Building and Testing

Dependencies: please see the correct OS-distribution section in the .gitlab-ci.yml

With all dependencies met, one is able to build and execute tests issuing the following bash commands:

# build mkdir output.dir/ && cd $_ cmake ../ && make # execute all tests (cd ../ && python tests/run_itests.py output.dir/mbusd)

Author:

Victor Antonovich (v.antonovich@gmail.com)

Contributors:

Andrew Denysenko (nitr0@seti.kr.ua):

  • RTS RS-485 data direction control
  • RTU response receiving by length

James Jarvis (jj@aprsworld.com):

  • file based RS-485 data direction control

Luuk Loeffen (luukloeffen@hotmail.com):

  • systemd support

Nick Mayerhofer (nick.mayerhofer@enchant.at):

  • CMake build system

License:

This project is distributed under the BSD license. See the LICENSE file for the full license text.